UPS systems

MP3100 3/1 phase online industrial UPS

Low-frequency online UPS for single-phase loads on a three-phase supply, built for industrial environments. 6–120 kVA.

Request a quote
MP3100 3/1 phase online industrial UPS

Overview

Division
UPS systems
Product line
Online UPS
Rating
6–120 kVA
Published models
12
Open in company profile

MP3100 is a new generation of transformer-based true online double-conversion UPS with full digital control, taking a three-phase input and delivering single-phase output. A high-speed microprocessor (MCU) and a programmable logic device (CPLD) run the control software, with sixth-generation low-loss, high-power IGBTs and a static switch as the power components.

  • Low-frequency true online double-conversion technology
  • LED + LCD display, operated from the LCD panel
  • IGBT PWM inverter, efficiency up to 93%
  • Wide input voltage range; optional 12-pulse rectifier (PF >0.96)
  • Intelligent battery management extends battery life
  • 0–100% load step without switching to bypass
  • Static bypass and manual maintenance bypass
  • 256-event real-time log
  • Selectable UPS, ECO or inverter mode
  • Generator compatible, auto restart
  • RS232 & RS485 standard; dry contacts or SNMP card optional
  • Optional N+1 redundant parallel, EPO and battery detecting module

Applications

Telecom and bankingSecurity and transportUtilities and manufacturingCommerce and governmentMedical equipment
ModelRatingDimensions (W×D×H)WeightNoise
MP3106K6 kVA / 4.8 kW450×600×1200 mm65 kg45–50 dB
MP3110K10 kVA / 8 kW450×600×1200 mm168 kg45–50 dB
MP3115K15 kVA / 12 kW450×600×1200 mm183 kg50–55 dB
MP3120K20 kVA / 16 kW450×600×1200 mm210 kg50–55 dB
MP3125K25 kVA / 20 kW450×600×1200 mm241 kg50–55 dB
MP3130K30 kVA / 24 kW450×600×1200 mm246 kg55–58 dB
MP3140K40 kVA / 32 kW600×720×1520 mm338 kg55–58 dB
MP3150K50 kVA / 40 kW600×720×1520 mm388 kg55–60 dB
MP3160K60 kVA / 48 kW600×720×1520 mm420 kg55–60 dB
MP3180K80 kVA / 64 kW980×800×1800 mm570 kg55–60 dB
MP31100K100 kVA / 80 kW980×800×1800 mm640 kg55–60 dB
MP31120K120 kVA / 96 kW980×800×1800 mm720 kg55–60 dB

Specifications

Common to all models in the series. Specifications are subject to change without notice.

Download datasheet

Rectifier (input)

Working principle
Low-frequency transformer-based true online double conversion
Phase
Three phase
Input power factor
Standard >0.9 (6-pulse rectifier + filter); optional >0.96 (12-pulse rectifier + filter)
Input voltage range
220/380 VAC (230/400 or 240/415 VAC) ±25%, 3P+N+PE; 110/208 V (120/220 or 277/480 VAC)
Input frequency range
50 Hz ±10% / 60 Hz ±10% (selectable)
Output ripple
<2%
Soft start
0–100% in 5 s

Charging & battery

Charging mode
Constant current, then constant voltage, with temperature compensation; automatic equalised / float switching
Float charging voltage
405 VDC
Equalised charging voltage
432 VDC
Temperature-compensated voltage
−3 mV/°C/cell
Charging current
0.1C (adjusted to battery capacity)
Battery type
VRLA / AGM / Gel, optional lithium
Battery capacity
7–999 Ah settable (to suit back-up time)
Quantity
30×12 V or 180×2 V (360 VDC nominal)

Inverter (output)

Phase
Single phase
Nominal voltage
220 VAC (230 or 240 VAC), 1P+N; optional 110 V (120 or 277 V)
Voltage regulation
±1% (stable load), ±3% (fluctuating load)
Output frequency
50 / 60 Hz <±0.5% (asynchronous)
Crest factor
>3:1
THD
Pure sine wave; linear load <3%, non-linear load <5%
Dynamic response
<±5% (0–100% load), recovery <10 ms
Unbalanced load voltage
<±5%
Overload capacity
115% continuous · 125% 10 min · 150% 1 min · 200% 1 s
Inverter efficiency
>93% (full load)

Bypass & protection

Bypass input voltage
220/380 VAC (230/400 or 240/415 VAC); optional 110 V
Bypass output voltage
220 VAC (230 or 240 VAC); optional 110 V
Transfer time
0 ms (static switch)
Input protection
Voltage and frequency over-limit, phase fault, phase loss
Output protection
Over-current, short circuit, over-voltage, low voltage
Battery protection
Over-charge, over-discharge
Temperature protection
Environment and inverter over-temperature
Hardware fault protection
Auxiliary power, breaker, power device over-current / over-voltage, etc.

General

Working environment
−10–40 °C, 30–90% RH, <2000 m (1% derating per 100 m, max. 4000 m)
Cooling
Forced ventilation
Communication
RS232 / RS485, optional dry contact, SNMP card
Parallel operation
Tandem hot backup or parallel connection
Anti-surge capacity
10/700 µs 5 kV; 8/20 µs 20 kA
Protection level
IP21
Safety
Vin-n Vout-n 2000 Vac, leakage <10 mA, insulation >2 MΩ (500 VDC)
Voltage versions
200–208–220 V (Ph-Ph) input and 100–110–120 V output version available

Specifying MP3100 3/1 phase online industrial UPS?

Share the load, site conditions and timeline, and our team will confirm the right model.

Discuss a requirement