UPS systems

HS/HTS 1/1 & 3/1 phase online UPS

High-frequency online UPS for single-phase loads: HS takes a single-phase supply (6–10 kVA), HTS a three-phase supply (10–20 kVA). 6–20 kVA.

Request a quote
HS/HTS 1/1 & 3/1 phase online UPS

Overview

Division
UPS systems
Product line
Online UPS
Rating
6–20 kVA
Published models
9
Open in company profile

HS (HTS) is an online double-conversion UPS. HS covers 6 kVA to 10 kVA (single-phase input, single-phase output); HTS covers 10 kVA to 20 kVA (three-phase input, single-phase output). Built on a 16-bit high-speed CPU and 40 kHz high-frequency technology, it is small, light and efficient, with zero transfer time and pure sine-wave output. Status is shown on the LCD, and digital self-detection and protection support remote monitoring.

  • High-frequency online double conversion
  • 35-degree adjustable LCD panel showing operation, load and battery status
  • Input power factor correction (PFC)
  • Wide input voltage and frequency range
  • 0.8 output power factor
  • Intelligent battery management extends battery life
  • Cold start and self-diagnosis at power-on
  • Input line and neutral detection
  • RS232 port, optional USB / SNMP card
  • Standard (internal battery) or long-backup (external battery) models
  • Tower and 3U rack models

Applications

Data processing centresHost systems and integrated computer networksISP servicesTelecomComputer rooms
ModelRatingPhaseInput voltage rangeInput power factorBuilt-in batteryCharge timeMax. charging currentSize (D×W×H)WeightNoiseRack height
HS-6KS6 kVA / 4800 W1/1120–275 VAC0.9912 V 7 Ah7 h to 90%1.0 A520×248×616 mm57 kg<55 dB—
HS-6KH6 kVA / 4800 W1/1120–275 VAC0.99—7 h to 90%1.0 A520×240×460 mm19.5 kg<55 dB—
HS-6KRH6 kVA / 4800 W1/1120–275 VAC0.9912 V 9 Ah7 h to 90%1.0 A647×484×130 mm19.5 kg<55 dB3U
HS-10KS10 kVA / 8000 W1/1120–275 VAC0.99—9 h to 90%1.0 A520×248×616 mm58.5 kg<55 dB—
HS-10KH10 kVA / 8000 W1/1120–275 VAC0.9912 V 9 Ah9 h to 90%1.0 A520×240×460 mm21.5 kg<55 dB—
HS-10KRH10 kVA / 8000 W1/1120–275 VAC0.99—9 h to 90%1.0 A647×484×130 mm21.5 kg<55 dB3U
HTS-10KH10 kVA / 8000 W3/1275–475 VAC0.95——4.0 A248×520×616 mm28.5 kg<58 dB—
HTS-15KH15 kVA / 12 kW3/1275–475 VAC0.95——4.0 A248×520×616 mm36.5 kg<58 dB—
HTS-20KH20 kVA / 16 kW3/1275–475 VAC0.95——4.0 A248×520×616 mm36.5 kg<58 dB—

Specifications

Common to all models in the series. Specifications are subject to change without notice.

Download datasheet

Input

Frequency range
46–54 Hz or 56–64 Hz

Output

Output voltage
220 VAC ±1% (battery mode)
Frequency range
47–53 Hz or 57–63 Hz (synchronised), 50/60 Hz ±0.3 Hz (battery mode)
Output power factor
0.8
Crest factor
3:1
Harmonic distortion
≤2% THD (linear load)
Transfer time
AC–DC: 0 ms; inverter to bypass: 4 ms (typical)
Waveform
Pure sine wave
Overload capacity
105–125%: bypass after 1 min · 125–135%: bypass after 30 s, output off after 1 min · >135%: bypass after 0.5 s

Efficiency

AC mode
89%
Battery mode
88%

Battery

DC voltage
192 VDC
Battery quantity
16
Charging voltage
219.2 VDC ±1%
Long-backup models (HS)
External battery bank (capacity and quantity to suit); max. charging current 4.0 A

General

Display
Load, battery capacity, AC mains, battery and bypass mode, fault indicator
Audible alarm
Battery mode every 4 s · battery low every 1 s · overload every 0.5 s · fault continuous
Humidity
20–90% RH @0–40 °C (non-condensing)
Smart RS232 (optional USB)
Windows 2000/2003/XP/Vista/2008/7, Linux, Unix
Optional SNMP
SNMP card for remote control, part no. DT520

Specifying HS/HTS 1/1 & 3/1 phase online UPS?

Share the load, site conditions and timeline, and our team will confirm the right model.

Discuss a requirement
WhatsAppGet help