HTT 3/3 phase high-frequency online UPS

Three-phase double-conversion online UPS with all-digital control, >96% efficiency and up to four units in parallel. 10–500 kVA.

Request a quote
HTT 3/3 phase high-frequency online UPS

Overview

Division
UPS systems
Product line
Online UPS
Rating
10–500 kVA
Published models
4

The HTT series is a double-conversion online UPS designed for every kind of power failure. It protects the loads from surges while keeping the output stable, accurate and reliable. All-digital control and parallel redundancy give room for future expansion and added safety.

  • Three-phase input and output, true online double conversion
  • Double DSP + double CPLD all-digital control
  • Input power factor up to 0.99, input THDi <5%
  • System efficiency >96%
  • Output voltage regulation <±1%
  • 200–482 V wide input range
  • Strong overload capacity and short-circuit protection
  • Digital parallel redundancy, up to 4 units
  • Three-stage intelligent charging extends battery life
  • Modular design for minimum repair time
  • EPO function

Applications

Data centres and IT / server roomsHealth careManufacturingSecurity systemsTelecom
ModelRatingPower ratingsEfficiencyDimensions (W×D×H)Weight without battery
HTT 10–50 kVA10–50 kVA10 kVA/8 kW, 15 kVA/12 kW, 20 kVA/16 kW, 30 kVA/30 kW, 40 kVA/36 kW, 50 kVA/45 kW>96%420×750×880 mm10/15 kVA 70 kg · 20 kVA 75 kg · 30 kVA 80 kg · 40–50 kVA 85 kg
HTT 60–120 kVA60–120 kVA60 kVA/60 kW, 80 kVA/72 kW, 100 kVA/90 kW, 120 kVA/108 kW>95%600×800×1250 mm60 kVA 210 kg
HTT 150–200 kVA150–200 kVA150 kVA/135 kW, 160 kVA/144 kW, 200 kVA/180 kW>95%600×1100×2000 mm150 kVA 415 kg · 200 kVA 460 kg
HTT 300–500 kVA300–500 kVA300 kVA/270 kW, 400 kVA/360 kW, 500 kVA/450 kW>96%1200×1100×2000 mm300 kVA 520 kg · 400 kVA 620 kg · 500 kVA 920 kg

Specifications

Common to all models in the series. Specifications are subject to change without notice.

Download datasheet

General

Topology
Double-conversion online UPS
Overload capacity
125% 10 min · 150% 1 min · >150% 200 ms (linear load)
UPS bypass
Automatic on overload or UPS failure
Parallel
4 units in parallel
IP rating
IP30 (removable dust filter)

Input

Phase
3 phase + N + PE
Voltage range
291–492 V (line-line) full load; 200–291 V linear derating
Frequency range
35–70 Hz
THDi
<3% (full linear load)
Power factor
0.995
Bypass range
−10% to +10% (customisable to −10/−30%, +10/+20%)

Output

Output voltage
380 VAC 3 phase + N + PE
Voltage regulation
<±1%
Phase lock range
50/60 Hz ±5 Hz (free-running 50/60 Hz ±0.01 Hz)
Output frequency
50/60 Hz ±0.01 Hz (follows mains when phase-locked)
Power factor
0.8 for 10–20 kVA (customisable to 1.0); 0.9 for 40–50 and 80–500 kVA; 1.0 for 30/60 kVA
Crest factor
3:1
THDu
<2.0% (linear load), <3% (non-linear load)
Voltage unbalance
Balanced load 0.5%; 100% unbalanced load 1%
Dynamic voltage transient
<3%
Transient recovery time
0 ms
Three-phase voltage deviation
Mains 0.4; battery 0.3
Transfer time
Mains to battery 0 ms; inverter to bypass 0 ms

Battery

Connection
Positive and negative series battery
Rated voltage
240 VDC (10–20 kVA); 480 VDC (30–500 kVA); customisable
Battery number
20 pcs/set (10–20 kVA); 40 pcs/set (30–500 kVA); 30–50 pcs/set optional
Charging current
20% of system power (battery capacity)

Environment & communication

Operating temperature
−10 to +40 °C
Storage temperature
−25 to +75 °C
Relative humidity
0–98%
Audible noise
<65 dB @100% load, intelligent fan speed control
Altitude
<1000 m; derating every 100 m from 1000 to 2000 m
Display
Touch screen LED + LCD
Communication
RS232, RS485, dry contacts; optional SNMP card (98-000182-00G)

Standards

Safety
EN/IEC 62040-1-1, YD/T 1095-2008
EMC
CE, EN/IEC 62040-2
Quality
ISO 9001:2000 and ISO 14001:1996