UPS systems

HP series online UPS

High-power tower online UPS with three-level soft-switching design, unity output power factor and up to 95.5% efficiency. 1–10 kVA.

Request a quote
HP series online UPS

Overview

Division
UPS systems
Product line
Online UPS
Rating
1–10 kVA
Published models
10
Open in company profile

The HP series is a 1–10 kVA tower online UPS built on a three-level, soft-switching design with active power factor correction. Input power factor reaches 0.99, full-load efficiency reaches 95.5% and ECO mode lifts it to 98.5%, while the high energy-density layout keeps the unit small. Digital control adds self-protection and fault diagnosis, and protects the load against voltage sags, high-voltage pulses, surges, harmonic distortion, noise and frequency fluctuation. S models carry internal batteries; L (long-backup) models connect to an external battery bank and share the same PCBA.

  • Three-level technique and soft-switch design
  • Active PFC, input power factor ≥0.99
  • Output power factor up to 1.0
  • Full-load efficiency up to 95.5%; ECO mode up to 98.5%
  • Selectable digital charger, 1–12 A, for different battery banks
  • Wide input range, 208/220/230/240 V selectable
  • Frequency settable to 50/60 Hz ±10 Hz for generator input
  • Same PCBA for standard and long-backup models — easy maintenance via LCD
  • Output voltage compensation for a transformer

Applications

IT and network equipmentSmall and medium data centresServer roomsTelecom base stationsFactory production-line controlRailway signallingSecurity and broadcast systemsOffice computers, printers and MPOS
ModelRatingBatteryChargerAC efficiencyBattery efficiencySize (L×W×H)Weight
HP-1KS1 kVA / 1000 W2×12V-9Ah (internal)1–2 A (1 A)94.5%89.5% @ 36 V285×144×225 mm9.25 kg
HP-1KL1 kVA / 1000 W36 V external1–12 A (5 A)94.5%89.5% @ 36 V285×144×225 mm5 kg
HP-2KS2 kVA / 2000 W6×12V-7Ah (internal)1–2 A (1 A)95.5%91.5% @ 72 V395×144×225 mm16 kg
HP-2KL2 kVA / 2000 W72 V external1–12 A (5 A)95.5%91.5% @ 72 V395×144×225 mm8.5 kg
HP-3KS3 kVA / 3000 W8×12V-7Ah (internal)1–2 A (1 A)95.5%91.5% @ 96 V410×190×325 mm28.2 kg
HP-3KL3 kVA / 3000 W96 V external1–12 A (5 A)95.5%91.5% @ 96 V395×144×225 mm9 kg
HP-6KS6 kVA / 6000 W20×12V-7Ah1–12 A (5 A)95%94.2% @ 240 V460×200×720 mm69.5 kg
HP-6KL6 kVA / 6000 W192 V / 240 V external1–12 A (5 A)95%94.2% @ 240 V460×200×360 mm14 kg
HP-10KS10 kVA / 10000 W20×12V-9Ah1–12 A (5 A)95%94.2% @ 240 V460×190×615 mm50.8 kg
HP-10KL10 kVA / 10000 W192 V / 240 V external1–12 A (5 A)95%94.2% @ 240 V395×190×325 mm9.6 kg

Specifications

Common to all models in the series. Specifications are subject to change without notice.

Download datasheet

Input

Input format
L+N+PE
Rated voltage
208/220/230/240 VAC
Voltage range
110–300 VAC (power limited at 110–176 and 280–300 VAC)
Frequency range
50/60 Hz ±6 Hz, ±10 Hz (settable)
Power factor
≥0.99
Harmonic distortion
1–3 kVA: ≤3% THD linear, ≤5% non-linear · 6–10 kVA: ≤5% linear, ≤8% non-linear

Output

Output format
L+N+PE
Voltage
208/220/230/240 VAC
Accuracy
±1%
Frequency
AC mode: same as input · Battery mode: 50/60 Hz ±1%
Harmonic distortion
1–3 kVA: ≤1% THD linear, ≤3% non-linear · 6–10 kVA: ≤2% linear, ≤5% non-linear
Power factor
1.0
Transfer time
0 ms (AC to battery)
Overload, AC mode
30 min @102–110% · 10 min @110–130% · 30 s @130–150% · 200 ms (1–3 kVA) / 500 ms (6–10 kVA) @>150%
Overload, battery mode
1–3 kVA: 1 min / 10 s / 3 s / 200 ms · 6–10 kVA: 10 min / 1 min / 10 s / 500 ms

Efficiency

AC mode
Up to 95.5% @220 VAC
ECO mode
Up to 98.5%
Battery mode
Up to 95.3% (6–10 kVA)

Environment & interface

Operating temperature
0–40 °C
Humidity
20–95% (non-condensing)
Storage temperature
−15–60 °C (battery 0–40 °C)
Altitude
<1000 m; derating above, max 4000 m (IEC 62040)
Display
LCD: mode, load, battery, input, output
Communication
1×USB, 1×RS232, 1×EPO
Standards
EN/IEC 61000, EN/IEC 62040, GB/T 4943, YD/T 1095, TLC

Specifying HP series online UPS?

Share the load, site conditions and timeline, and our team will confirm the right model.

Discuss a requirement
WhatsAppGet help